The WT401R is a customized, IoT-enabled controller for RO purifiers. It runs the pump, valves, UV lamp and flush, blends the purified water to a TDS set point in timed pulses, checks the membrane every cycle, reads the TDS probes, flow meter and switches, shows the status on a 3-digit display and sends every reading and alert to your server over 4G. Open the tap, cut the inlet pressure, change the TDS set point, wear the membrane or dim the UV lamp below and watch it react.
Yes. The WT401R has 4G built in, so TDS in and out, the blend, membrane rejection, total flow, running hours, and faults and alerts such as low pressure, tank full, UV lamp fail and a worn membrane go to your server over 4G, and every purifier can be watched remotely.
It runs the purifier itself: terminal 4 switches 24 V to the booster pump, inlet valve and UV lamp, terminal 5 opens the TDS mixing valve and terminal 13 the flush valve. It reads both TDS probes, the flow meter, the low-pressure switch and the tank-full switch, and shows the status on a 3-digit display.
With timed pulses of the mixing valve on terminal 5, which has a needle valve in series. While the purifier is producing, the valve opens for part of every 60-second cycle. The second TDS probe, right after the mixing point, reads pure RO water while the valve is closed and the blend while it is open. From those two readings and TDS in, the controller sets how long the valve opens in the next cycle, so the water reaching the tank averages the set point, 100 ppm by default. The valve switches at most twice a minute.
It flushes the membrane at every start, stops on low inlet pressure and flags a failed UV lamp. Feed water never makes up more than 25 % of the blend, and mixing stops when the feed TDS is above 1500 ppm or a TDS probe fails. The pure-RO reading gives the membrane's rejection every cycle; below 85 %, a membrane alert goes to your server over 4G.
It steps through TDS in, TDS out, total flow and running hours. A fault comes first and blinks: LPF for low inlet pressure, tF for a full tank and ULF for a failed UV lamp.
The low-pressure switch opens, the controller stops the pump and closes the inlet valve, and the display shows LPF. When the pressure is back it waits, then restarts with a flush.